Menu
Back
  1. Products
  2. Automation technology - Sensors and actuators
  3. M12-A
  4. M12 Male cable connector, Contacts: 12, shielded, moulded on the cable, IP67, UL, PUR, black, 12 x 0.25 mm², 2 m
Part no.: 77 3529 0000 50712-0200

M12 Male cable connector, Contacts: 12, shielded, moulded on the cable, IP67, UL, PUR, black, 12 x 0.25 mm², 2 m

M12-A, series 763, Automation Technology - Sensors and Actuators
Available numbers of contacts
(Standard 2 m and 5 m. Other lengths are available on request.)
Compare product
Downloads
General features
Moreless
Part no. 77 3529 0000 50712-0200
Connector design Male cable connector
Type standard DIN EN 61076-2-101
Cable length 2 m (Standard 2 m and 5 m. Other lengths are available on request.)
Version Connector pin straight
Connector locking system screw
Termination moulded on the cable
Degree of protection IP67
Cross-sectional area 0.25 mm² / AWG 24
Temperature range from/to -25 °C / 90 °C
Mechanical operation > 100 Mating cycles
Weight (g) 260
Customs tariff number 85444290
Country of Origin DE
Rated voltage 30 V
Rated impulse voltage 800 V
Rated current 1.5 A
Insulation resistance ≥ 1010 Ω
Pollution degree 3
Overvoltage category II
Insulating material group II
EMC compliance shielded
Shield connection Shield on the threaded ring
Housing material PUR
Contact body material PUR
Contact material CuZn (brass)
Contact plating Au (gold)
Locking material CuZn (brass)
REACH SVHC CAS 7439-92-1 (Lead)
SCIP number 63a918a5-7b5c-498e-b9fe-25247b65831e
ETIM 9.0 EC002638
Cable data
Moreless
Structure of the cable
Cable diameter 5.75 mm
Cross section 12 x 0.25 mm²
Sheath material PUR
Single-lead insulation PP9Y halogen-free
Single-lead structure 19 x 0.127 mm
Cable color black
Electrical properties
Cable Insulation resistance > 1000 Ω/Km
Operating voltage 300 V
Mechanical properties
Bending radius, fixed cable 5 x Ø
Bending radius, moving cable 10 x Ø
Thermal properties
Temperature range cable in move from/to -30 °C / 105 °C
Temperature range cable fixed from/to -50 °C / 105 °C
Other features
Halogen free yes
Security notices
  1. The connector must not be plugged or unplugged under load. Non-observance and improper use can result in personal injury.
  2. The connectors have been developed for applications in plant engineering, control and electrical equipment construction. The user is responsible for checking whether the connectors can also be used in other areas of application.
  3. Connectors which are used in circuits with voltages dangerous to the touch may only be installed and used by, or under the supervision of, persons with electrical engineering training, taking into account the applicable regulations and standards.
  4. To lock the cable connector with the device connector, the threaded ring is tightened "hand-tight" (approx. 60 cNm).
  5. The protection class specification applies on condition that the four mounting holes are made as blind holes.
Downloads
Data sheet
Data sheet 77 3529 0000 50712-0200
PDF
Data sheet, Data sheet 77 3529 0000 50712-0200
Certificates
UL certificate
PDF, 1.29 MB
REACH
77 3529 0000 50712-0200
PDF
RoHS
77 3529 0000 50712-0200
PDF
China RoHS
77 3529 0000 50712-0200
PDF
CAD files
Select required format
M12-A
77 3529 0000 50712-0200